Duct noise is proportional to velocity. Doubling velocity adds roughly 16 dB. The duct size you choose locks in the noise level permanently.
Velocity drives noise
Velocity = CFM / Duct Area
1,200 CFM through two different ducts:
18" round: Area = 1.77 ft² V = 679 FPM → quiet
14" round: Area = 1.07 ft² V = 1,122 FPM → noisy (+8 dB)
Same airflow. 65% more velocity. 8 dB more noise.
ASHRAE recommended max velocities
Space type Max FPM NC rating
──────────────────────────────────────────
Residential 400–700 NC-25
Libraries, studios 500–700 NC-25–30
Private offices 600–800 NC-30–35
Open offices 700–1,000 NC-35–40
Retail, restaurants 800–1,200 NC-40–45
Industrial 1,000–2,500 NC-50+
NC = Noise Criteria. Lower NC = quieter space = lower max velocity.
Where noise gets worse: fittings
Straight duct noise is predictable. Fittings generate turbulence noise 10–20 dB louder:
Fitting Added noise
──────────────────────────────────────
Sharp 90° elbow (no vanes) +12–18 dB
Vaned 90° elbow +4–8 dB
Tee branch +8–14 dB
Abrupt transition +6–12 dB
Takeoff (no scoop) +8–15 dB
A vaned elbow is 8–12 dB quieter than unvaned at the same velocity. That is the difference between hearing the duct and not hearing it.
Rectangular duct adds breakout noise
Round duct: curved surface resists vibration
minimal panel noise
Rectangular duct: flat panels vibrate (drumming)
wider panel = lower frequency = louder
36" wide panel >> 12" wide panel
This is another reason extreme aspect ratios fail — a 36×6 duct is not just higher friction, it is also louder than a 12×8 duct of the same area.
The cost comparison
Fix at design stage:
Select 18" instead of 14" duct
Cost difference: ~$2–5/linear foot
For 100 ft run: $200–500
Fix after construction:
Duct silencer: $2,000–10,000 installed
Duct replacement: $5,000–25,000
Ceiling repair: additional cost
Tenant disruption: priceless
The check
Before committing to a duct size:
1. Calculate velocity: V = CFM / Area
2. Look up NC rating for the space type
3. Compare velocity to ASHRAE max for that NC
4. If over → select next larger duct size
This takes 30 seconds. The noise complaint lasts the life of the building.